Report header
Shown in the top band of the report — consultant name on the left, contact line beneath, assessment date on the right.
1 · Consumer & connection
All fields are free text — nothing is pre-filled.
2 · Basis of assessment & computed ratio
IL is computed automatically from the 12-month demand and system voltage in section 1 (IL = kVA ÷ √3 ÷ VLL). The TDD limit comes from the table (Table 2 ≤69 kV · Table 3 69–161 kV · Table 4 >161 kV) and the Isc/IL band; both are auto-selected from the voltage and Isc÷IL, and can be overridden below. Choose whether TDD is taken from the data or computed. The applicable table, band and TDD limit appear live in the next card.
Auto-selected IEEE 519 current limits
Table chosen automatically from the system voltage (Table 2 ≤69 kV · Table 3 69–161 kV · Table 4 >161 kV); Isc/IL picks the row. Live preview of the per-group base limits, before the daily/weekly factor.
Upload measurement files
Add the seven daily 3-second files together or one by one, plus the 10-minute weekly file. CSV or XLSX. Files stay in your browser. Each is auto-classified; override with the dropdown. Adding is instant — the full file is read only when you run the analysis. Phase 1 processes current.
GridVis export, e.g. “…Harmonic Current L1 [3s] (A)”. An optional “1. Harmonic Current …” fundamental is carried as reference.
No results yet
Add files in step 2 and run the analysis.
Generate report
Page 1 — consumer & technical particulars. Page 2 — TDD compliance for all 7 days plus weekly, across all three percentiles (daily VST 99th, weekly ST 99th, weekly ST 95th). Page 3 onward — individual harmonic orders with PASS/FAIL.